Voltage Drop Formula: How to Calculate Voltage Drop

Voltage drop formula illustration showing a battery connected to a light bulb through electrical wires.
Voltage Drop Formula: Understanding voltage loss in DC and AC electrical circuits.

Voltage drop is the reduction in electrical voltage that occurs as current travels through a wire or cable. Every conductor has some resistance, so the voltage available at the load is lower than the voltage supplied at the source.

The voltage drop formula helps you estimate this loss in DC, single-phase AC, and three-phase electrical circuits. It is useful when checking long cable runs, selecting conductors, and determining whether equipment will receive enough voltage to operate properly.

You can use the formulas and examples below to calculate voltage drop manually, or use our Voltage Drop Calculator to check your own circuit.

What Is the Voltage Drop Formula?

For DC and single-phase circuits, a commonly used resistance-based formula is:

Voltage drop for DC or single-phase circuits:

[V_D=\frac{2KIL}{CM}]

Voltage drop for balanced three-phase circuits:

[V_D=\frac{1.732KIL}{CM}]

Here, the K-factor method uses conductor resistance and cross-sectional area to estimate voltage loss. The formulas are commonly expressed using American Wire Gauge (AWG) conductor sizes and circular mils.

What Do the Variables Mean?

SymbolMeaningUnit
(V_D)Voltage dropVolts (V)
(K)Conductor resistance constantΩ·circular mils per foot
(I)Load currentAmperes (A)
(L)One-way conductor run lengthFeet (ft)
(CM)Conductor cross-sectional areaCircular mils

For an approximate calculation at a conductor temperature of 75°C, commonly used K values are 12.9 for copper and 21.2 for aluminum. Actual conductor resistance depends on temperature and the conductor’s properties.

These formulas use one-way length because the factor of 2 already accounts for the outgoing and return conductors in a two-wire DC or single-phase circuit.

How to Calculate Voltage Drop

Follow these steps to calculate voltage drop using the K-factor formula.

  1. Identify the circuit voltage and load current.
  2. Measure the one-way cable run from the source to the load.
  3. Identify the conductor material and wire size.
  4. Find the conductor’s cross-sectional area in circular mils.
  5. Select the appropriate formula for DC, single-phase, or balanced three-phase service.
  6. Calculate the voltage drop in volts.
  7. Divide the voltage drop by the source voltage and multiply by 100 to find the percentage.

Use consistent units throughout the calculation. The K-factor formulas above require the run length in feet and conductor area in circular mils.

DC Voltage Drop Formula

For a two-wire DC circuit, use:

[V_D=\frac{2KIL}{CM}]

The factor of 2 accounts for the full electrical path: current travels to the load on one conductor and returns on the other.

Example: Calculate Voltage Drop in a 12V DC Circuit

Suppose a 12V DC system has these specifications:

  • Supply voltage: 12V
  • Load current: 20A
  • One-way cable length: 25 feet
  • Conductor: 10 AWG copper
  • Conductor area: 10,380 circular mils
  • K-factor: 12.9

Substitute the values into the formula:

[V_D=\frac{2\times12.9\times20\times25}{10,380}]

[V_D\approx1.24\text{ V}]

The percentage voltage drop is:

[%\text{ Drop}=\frac{1.24}{12}\times100]

[%\text{ Drop}\approx10.3%]

The estimated voltage at the load is:

[V_{\text{load}}=12-1.24=10.76\text{ V}]

This is a substantial drop for a 12V system. Check the equipment’s operating-voltage requirements, and select a suitable conductor based on both voltage drop and current-carrying capacity.

Single-Phase AC Voltage Drop Formula

For a simplified single-phase circuit, the formula is:

[V_D=\frac{2KIL}{CM}]

The factor of 2 accounts for the outgoing and returning current paths. This resistance-based formula is useful for estimates, particularly with smaller conductors and circuits where reactance has a limited effect.

Example: Calculate Voltage Drop in a 240V Circuit

Consider a single-phase circuit with the following specifications:

  • Supply voltage: 240V
  • Load current: 30A
  • One-way cable length: 150 feet
  • Conductor: 10 AWG copper
  • Conductor area: 10,380 circular mils
  • K-factor: 12.9

Calculate the voltage drop:

[V_D=\frac{2\times12.9\times30\times150}{10,380}]

[V_D\approx11.2\text{ V}]

Calculate the percentage:

[%\text{ Drop}=\frac{11.2}{240}\times100]

[%\text{ Drop}\approx4.7%]

The estimated voltage at the load is approximately 228.8V.

This example shows why cable length matters. A conductor that carries the load current safely may still produce more voltage drop than the design target allows.

Three-Phase Voltage Drop Formula

For a balanced three-phase circuit, a commonly used K-factor approximation is:

[V_D=\frac{1.732KIL}{CM}]

The multiplier 1.732 is the square root of 3. It accounts for the relationship between the phase quantities in a balanced three-phase system.

Example: Calculate Voltage Drop in a 480V Circuit

Assume a balanced three-phase circuit has these values:

  • Supply voltage: 480V line-to-line
  • Load current: 50A
  • One-way run length: 200 feet
  • Conductor: 6 AWG copper
  • Conductor area: 26,240 circular mils
  • K-factor: 12.9

Calculate the voltage drop:

[V_D=\frac{1.732\times12.9\times50\times200}{26,240}]

[V_D\approx8.5\text{ V}]

The percentage voltage drop is:

[%\text{ Drop}=\frac{8.5}{480}\times100]

[%\text{ Drop}\approx1.8%]

This is the estimated voltage drop using the simplified formula. For larger AC conductors, long runs, low power factors, or critical installations, a calculation based on conductor impedance may be more appropriate.

Voltage Drop Percentage Formula

Voltage drop percentage shows how much voltage is lost relative to the source voltage.

Use this formula:

[%\text{ Voltage Drop}=\frac{V_D}{V_S}\times100]

Where:

  • (V_D) is the calculated voltage drop in volts.
  • (V_S) is the source voltage.

For example, if a 120V circuit has a calculated voltage drop of 3.6V:

[%\text{ Drop}=\frac{3.6}{120}\times100=3%]

The percentage makes it easier to compare voltage loss across circuits with different supply voltages.

What Is an Acceptable Voltage Drop?

A suitable voltage drop depends on the applicable electrical code, the equipment being supplied, the installation conditions, and the project requirements.

In the United States, the National Electrical Code (NEC) includes informational-note recommendations commonly associated with approximately 3% voltage drop on an individual branch circuit or feeder and 5% combined voltage drop for feeder and branch circuits. These figures are not universal legal limits for every circuit, and requirements can vary by application and locally adopted code.

Check the electrical code adopted in your jurisdiction, the equipment manufacturer’s instructions, and any project-specific requirements before choosing a design target.

A low-voltage system may need a tighter percentage target because even a small loss in volts can represent a significant proportion of the supply voltage.

How to Calculate the Required Wire Size

If you know the maximum acceptable voltage drop, you can rearrange the single-phase or two-wire DC formula to estimate the required conductor area.

[CM=\frac{2KIL}{V_D}]

For a balanced three-phase circuit using the same simplified method:

[CM=\frac{1.732KIL}{V_D}]

For example, consider the 12V DC circuit above. If the target is 3%, the maximum voltage drop is:

[V_D=12\times0.03=0.36\text{ V}]

The required circular-mil area is:

[CM=\frac{2\times12.9\times20\times25}{0.36}]

[CM\approx35,833]

Choose a suitable standard conductor size with at least this cross-sectional area, then verify ampacity, temperature ratings, terminal limitations, overcurrent protection, installation conditions, and local code requirements. A voltage-drop calculation alone does not establish a safe or code-compliant conductor size.

For a quick estimate, use our Voltage Drop Calculator to compare your circuit values.

What Is the Difference Between Voltage Drop and Ampacity?

Voltage drop and ampacity measure two different things.

Voltage drop describes how much voltage is lost as current flows through a conductor.

Ampacity is the current-carrying capacity of a conductor under specified installation conditions.

A wire can meet the required ampacity and still produce excessive voltage drop over a long run. Conversely, choosing a larger wire to reduce voltage drop does not remove the need to verify its suitability for the circuit.

Always evaluate both factors when selecting conductors.

How to Reduce Voltage Drop

If the calculated voltage drop is too high, consider the following options:

  • Increase conductor size: A larger conductor generally has lower resistance and reduces voltage drop.
  • Shorten the cable run: A shorter conductor length reduces resistance.
  • Review the system design: Where appropriate, a higher distribution voltage can reduce current for the same power demand.
  • Compare conductor materials: Copper generally has lower resistance than aluminum for comparable conductor dimensions.
  • Check operating conditions: Conductor temperature, installation method, and AC impedance can affect the result.

Any design change must comply with applicable electrical codes and equipment requirements. Have a qualified electrician or electrical engineer review installations where safety or equipment performance is at stake.

Frequently Asked Questions

What is the basic voltage drop formula?

For DC or single-phase circuits, a commonly used K-factor formula is (V_D=2KIL/CM). For balanced three-phase circuits, the corresponding approximation is (V_D=1.732KIL/CM).

How do you calculate voltage drop percentage?

Divide the calculated voltage drop by the source voltage and multiply by 100. For example, a 3.6V drop on a 120V supply equals 3%.

Do I use one-way or round-trip cable length?

Use the one-way length when applying the formulas shown in this guide. The factor of 2 in the DC and single-phase formulas already accounts for the return conductor.

Why is voltage drop more important in a 12V system?

A small loss in volts represents a larger percentage of a 12V supply than it does in a higher-voltage system. This can affect equipment that requires a minimum operating voltage.

Is the same formula used for DC and AC circuits?

The simplified resistance-based formula is commonly used for DC and can estimate voltage drop in some AC circuits. For AC circuits where reactance and power factor are significant, an impedance-based method may be needed.

Is 3% voltage drop a mandatory electrical code limit?

Not universally. In the US, the NEC’s familiar 3% branch-circuit and feeder figures appear in informational notes for general applications. Applicable requirements depend on the adopted code, the circuit type, and the installation.

Can a larger wire reduce voltage drop?

Yes. A larger conductor generally has lower resistance, which reduces voltage drop for a given current and cable length. The final conductor size must also satisfy ampacity and other installation requirements.

Final Thoughts

The voltage drop formula helps you estimate how much voltage is lost between an electrical source and its load. By using the correct circuit formula, conductor data, current, and one-way cable length, you can calculate the voltage drop in volts and as a percentage of the supply.

For practical installations, use the calculation as one part of conductor selection – not as a replacement for ampacity checks, applicable electrical codes, or professional review.

Use our Voltage Drop Calculator to check your values, and explore the Electrical Wire Gauge Calculator for further conductor-sizing guidance.

Technical reference: Consult the applicable edition of NFPA 70 (National Electrical Code), relevant conductor-resistance tables, and the equipment manufacturer’s installation instructions. For background on the K-factor method and its limitations, see the International Association of Electrical Inspectors’ voltage drop calculations guide.